Monday 2 December 2013

Luminous Higher KVA Inverters


Being one of the leaders in innovation, design sensibility and sales distribution network, we are offering Power Back Up Solutions and Power Back Up System that includes Power Digital Inverters, Online UPS Systems, Line Interactive UPS Systems, Inverter Batteries (Lead Acid and VRLA).

Applications

BPO’s, Call Centers, Multiplexes, Shopping malls, Banking, IT Sector, Hospitals.

Features

  • Pure sine wave
  • High efficiency
  • Regulated output
  • Suitable for 3 phase unbalanced load
  • Low harmonic distortion
  • Designed for high inductive load
  • IGBT based PWM technology

inverter dealers in delhi-ncr


Specifications of HIGHER RATING INVERTERS


SinglePhase Input/single phase Output Three-Phase input/Three phase output
RATING 15KVA TO 50 KVA 15 KVA TO 150 KVA
INPUT AC 170V to 270V AC 320V to 470V AC
DC Voltage 180VDC For 15/20 KVA. 360 VDC above 20KVA 360VDC
Frequency 50Hz + 10%
OUTPUT Technology IGBT based
Output Voltage 230V AC Single Phase 400V / 415V AC Three Phase
Voltage Regulation + 2% Maximum
Frequency 50Hz + 0.1Hz
Waveform PWM Sine Wave
Harmonic Distortion Less than 3% on linear load
Inverter Efficiency > 93% for 360 VDC and above >90% for 180 VDC
Power Factor 0.8
Overload 125% for 5 Minutes 150% for 60 sec
Crest Factor 3:1
Transient Response + 4% under full load change and corrected within 5 cycles.
Phase Displacement
120o +/- 1o
Audible Noise Less than 45 dB 1 Meter
METERING Microprocessor Based Digital LCD Meter Out Voltage, Output current & Frequency, DC Voltage, Battery and Load Percentage R, Y, B, Output voltage, Output current & Frequency, DC Voltage, Battery and Load Percentage
CHANGE - OVER Static Switch Bi-directional
Manual bypass Provided
ISOLATION OF POWER Input MCB Provided for charger
Battery HRC Fuse
Indiaction & Alarms Mains On Indication
Inverter On Indication
Mains Fail Indication & Alarm
DC Low Indication
Fault Indication
Output Overload IIndication
ENVIRONMENTAL Operating Temperature 0oC  to 50o C
Humidity Max 95 %, Non -Condensing
PROTECTIONS Output Overload & Short circuit, Under & Over Voltage, DC Under & Over voltage input Under & Over voltage, Single Phasing & Phase unbalance (for 3 - Ph Input only)

0 comments:

Post a Comment